/usr/sbin/fence_apc_snmp is in fence-agents 3.1.5-2ubuntu2.
This file is owned by root:root, with mode 0o755.
The actual contents of the file can be viewed below.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 | #!/usr/bin/python
# The Following agent has been tested on:
# - APC Switched Rack PDU (MB:v3.7.0 PF:v2.7.0 PN:apc_hw02_aos_270.bin AF1:v2.7.3 AN1:apc_hw02_aos_270.bin
# AF1:v2.7.3 AN1:apc_hw02_rpdu_273.bin MN:AP7930 HR:B2) - SNMP v1
# - APC Web/SNMP Management Card (MB:v3.8.6 PF:v3.5.8 PN:apc_hw02_aos_358.bin AF1:v3.5.7 AN1:apc_hw02_aos_358.bin
# AF1:v3.5.7 AN1:apc_hw02_rpdu_357.bin MN:AP7900 HR:B2) - SNMP v1 and v3 (noAuthNoPrivacy,authNoPrivacy, authPrivacy)
# - APC Switched Rack PDU (MB:v3.7.0 PF:v2.7.0 PN:apc_hw02_aos_270.bin AF1:v2.7.3 AN1:apc_hw02_rpdu_273.bin
# MN:AP7951 HR:B2) - SNMP v1
import sys, re, pexpect
sys.path.append("/usr/share/fence")
from fencing import *
from fencing_snmp import *
#BEGIN_VERSION_GENERATION
RELEASE_VERSION="3.1.5"
BUILD_DATE="(built Mon Feb 6 23:36:21 UTC 2012)"
REDHAT_COPYRIGHT="Copyright (C) Red Hat, Inc. 2004-2010 All rights reserved."
#END_VERSION_GENERATION
### CONSTANTS ###
# oid defining fence device
OID_SYS_OBJECT_ID='.1.3.6.1.2.1.1.2.0'
### GLOBAL VARIABLES ###
# Device - see ApcRPDU, ApcMSP, ApcMS
device=None
# Port ID
port_id=None
# Switch ID
switch_id=None
# Classes describing Device params
class ApcRPDU:
# Rack PDU
status_oid= '.1.3.6.1.4.1.318.1.1.12.3.5.1.1.4.%d'
control_oid= '.1.3.6.1.4.1.318.1.1.12.3.3.1.1.4.%d'
outlet_table_oid='.1.3.6.1.4.1.318.1.1.12.3.5.1.1.2'
ident_str="APC rPDU"
state_on=1
state_off=2
turn_on=1
turn_off=2
has_switches=False
class ApcMSP:
# Master Switch+
status_oid= '.1.3.6.1.4.1.318.1.1.6.7.1.1.5.%d.1.%d'
control_oid= '.1.3.6.1.4.1.318.1.1.6.5.1.1.5.%d.1.%d'
outlet_table_oid='.1.3.6.1.4.1.318.1.1.6.7.1.1.4'
ident_str="APC Master Switch+"
state_on=1
state_off=2
turn_on=1
turn_off=3
has_switches=True
class ApcMS:
# Master Switch - seems oldest, but supported on every APC PDU
status_oid= '.1.3.6.1.4.1.318.1.1.4.4.2.1.3.%d'
control_oid= '.1.3.6.1.4.1.318.1.1.4.4.2.1.3.%d'
outlet_table_oid='.1.3.6.1.4.1.318.1.1.4.4.2.1.4'
ident_str="APC Master Switch (fallback)"
state_on=1
state_off=2
turn_on=1
turn_off=2
has_switches=False
### FUNCTIONS ###
def apc_set_device(conn,options):
global device
agents_dir={'.1.3.6.1.4.1.318.1.3.4.5':ApcRPDU,
'.1.3.6.1.4.1.318.1.3.4.4':ApcMSP,
None:ApcMS}
# First resolve type of APC
apc_type=conn.walk(OID_SYS_OBJECT_ID)
if (not ((len(apc_type)==1) and (agents_dir.has_key(apc_type[0][1])))):
apc_type=[[None,None]]
device=agents_dir[apc_type[0][1]]
conn.log_command("Trying %s"%(device.ident_str))
def apc_resolv_port_id(conn,options):
global port_id,switch_id,device
if (device==None):
apc_set_device(conn,options)
# Now we resolv port_id/switch_id
if ((options["-n"].isdigit()) and ((not device.has_switches) or (options["-s"].isdigit()))):
port_id=int(options["-n"])
if (device.has_switches):
switch_id=int(options["-s"])
else:
table=conn.walk(device.outlet_table_oid,30)
for x in table:
if (x[1].strip('"')==options["-n"]):
t=x[0].split('.')
if (device.has_switches):
port_id=int(t[len(t)-1])
switch_id=int(t[len(t)-3])
else:
port_id=int(t[len(t)-1])
if (port_id==None):
fail_usage("Can't find port with name %s!"%(options["-n"]))
def get_power_status(conn,options):
global port_id,switch_id,device
if (port_id==None):
apc_resolv_port_id(conn,options)
oid=((device.has_switches) and device.status_oid%(switch_id,port_id) or device.status_oid%(port_id))
(oid,status)=conn.get(oid)
return (status==str(device.state_on) and "on" or "off")
def set_power_status(conn, options):
global port_id,switch_id,device
if (port_id==None):
apc_resolv_port_id(conn,options)
oid=((device.has_switches) and device.control_oid%(switch_id,port_id) or device.control_oid%(port_id))
conn.set(oid,(options["-o"]=="on" and device.turn_on or device.turn_off))
def get_outlets_status(conn, options):
global device
result={}
if (device==None):
apc_set_device(conn,options)
res_ports=conn.walk(device.outlet_table_oid,30)
for x in res_ports:
t=x[0].split('.')
port_num=((device.has_switches) and "%s:%s"%(t[len(t)-3],t[len(t)-1]) or "%s"%(t[len(t)-1]))
port_name=x[1].strip('"')
port_status=""
result[port_num]=(port_name,port_status)
return result
# Define new options
def apc_snmp_define_defaults():
all_opt["snmp_version"]["default"]="1"
all_opt["community"]["default"]="private"
# Main agent method
def main():
device_opt = [ "help", "version", "agent", "quiet", "verbose", "debug",
"action", "ipaddr", "login", "passwd", "passwd_script",
"test", "port", "separator", "no_login", "no_password",
"snmp_version", "community", "snmp_auth_prot", "snmp_sec_level",
"snmp_priv_prot", "snmp_priv_passwd", "snmp_priv_passwd_script",
"udpport","inet4_only","inet6_only",
"power_timeout", "shell_timeout", "login_timeout", "power_wait" ]
atexit.register(atexit_handler)
snmp_define_defaults ()
apc_snmp_define_defaults()
options=check_input(device_opt,process_input(device_opt))
## Support for -n [switch]:[plug] notation that was used before
if ((options.has_key("-n")) and (-1 != options["-n"].find(":"))):
(switch, plug) = options["-n"].split(":", 1)
if ((switch.isdigit()) and (plug.isdigit())):
options["-s"] = switch
options["-n"] = plug
if (not (options.has_key("-s"))):
options["-s"]="1"
docs = { }
docs["shortdesc"] = "Fence agent for APC over SNMP"
docs["longdesc"] = "fence_apc_snmp is an I/O Fencing agent \
which can be used with the APC network power switch. It logs \
into a device via SNMP and reboots a specified outlet. It supports \
SNMP v1 and v3 with all combinations of authenticity/privacy settings."
docs["vendorurl"] = "http://www.apc.com"
show_docs(options, docs)
# Operate the fencing device
result = fence_action(FencingSnmp(options), options, set_power_status, get_power_status, get_outlets_status)
sys.exit(result)
if __name__ == "__main__":